Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM03722
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/01/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
01/04/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS MECHANICAL ROOM #123 |
|
12/31/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK X-RAY ROOM WALLS 109, 110, 133 |
|
12/27/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) REMOVE SHEETROCK FROM X-RAY ROOM WALLS 2) INSTALL BONDING FROM CT CAN TO TERM CAN ON 4" NIPPLES NEC 250.92 3) LOCK OUT SERVICE DISCONNECT AND RECALL WHEN READY TO ENGERGIZE BRANCH CIRCUITS |
|
12/03/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS EXCEPT RMS 109, 110, 123, 133 |
|
11/20/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK FLOOR BOXES RMS 108, 125, 126, 127, 128, 129, 130 2. OK WALLS RMS 101, 102, 103, 104, 105, 106, 117, 116 |