Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* 1) CHECK FOR $108.00 DEVELOPMENT SERVICES |
|
| 09/18/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* AFTER HOURS INSP. $108.00 CHECK ON SITE 1. MAINTAIN DEDICATED SPACE BELOW PANEL 110.26 2. GROUNDED CONDUCTOR TO BE WHITE ENTIRE LENGTH IN A RACEWAY 3. INSTALL ALL STRANDS UNDER TERMINAL LUG - DO NOT FORK CONDUCTOR 4. TIGHTEN LOOSE FITTINGS 5. SUPPORT CAR FLEX, SUPPORT RISER 6. FINISH DRIVING GROUND RODS 7. NM & SE CABLE TO BE IN A NON-FLEXIBLE RACEWAY ON EXTERIOR 8. SECURE CABLES TO BOX 9. MAINTAIN WORKING CLEARANCE AT SUB-PANEL 10. NEED PERMANENT METAL ADDRESS SCREWED OR RIVETED TO SERVICE 11. LABEL CIRCUITS AS PER 408.4 - NO ABBREVIATIONS 12. BURY CONDUIT AS PER 300.5 13. SUPPORT GROUND WIRE UP OFF OF ROOF 14. CLEAN SURFACE UNDER CLAMPS TO MAKE CONTACT 15. AC DISCONNECT TO BE AS PER 440.14 NOT ON ACCESSIBLE PANEL |