Permit: T07CM03705

Parcel: 133050390


Addresses:

8801 E DEXTER DR

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
09/19/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
1) CHECK FOR $108.00 DEVELOPMENT SERVICES
09/18/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
AFTER HOURS INSP. $108.00 CHECK ON SITE

1. MAINTAIN DEDICATED SPACE BELOW PANEL 110.26
2. GROUNDED CONDUCTOR TO BE WHITE ENTIRE LENGTH IN A RACEWAY
3. INSTALL ALL STRANDS UNDER TERMINAL LUG - DO NOT FORK CONDUCTOR
4. TIGHTEN LOOSE FITTINGS
5. SUPPORT CAR FLEX, SUPPORT RISER
6. FINISH DRIVING GROUND RODS
7. NM & SE CABLE TO BE IN A NON-FLEXIBLE RACEWAY ON EXTERIOR
8. SECURE CABLES TO BOX
9. MAINTAIN WORKING CLEARANCE AT SUB-PANEL
10. NEED PERMANENT METAL ADDRESS SCREWED OR RIVETED TO SERVICE
11. LABEL CIRCUITS AS PER 408.4 - NO ABBREVIATIONS
12. BURY CONDUIT AS PER 300.5
13. SUPPORT GROUND WIRE UP OFF OF ROOF
14. CLEAN SURFACE UNDER CLAMPS TO MAKE CONTACT
15. AC DISCONNECT TO BE AS PER 440.14 NOT ON ACCESSIBLE PANEL