Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/24/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
| 01/23/2008 | ELECTRIC - FINAL | Partial Approval | ROOF: 1. PROVIDE MAINTENANCE RECEPTACLE PER 210.63 2. PROTECT SEAL TITE FROM SHARP METAL EDGES AND DO NOT INSTALL THROUGH COVER ROOM 101: 1. PLEASE PROVIDE PAPERWORK FOR TRIM KIT |
|
| 01/22/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. EXPOSED CONDUCTORS ON OUTSIDE OF FIXTURE |
|
| 01/18/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" -- 314.20 2. PANEL DIRECTORIES TO BE AS PER 408.4 3. NEED PLAN REVISION 4. PROVIDE OCCUPANCY SENSOR PAPERWORK |