Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 01/14/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILINGS PHASE 2 |
|
| 01/11/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. USE APPROVED FIXTURE FOR DRYWALL 2. STRAP CONDUITS TO STRUT RACKS OK TO TILE EXCEPT AREA OF CONDUIT RUN |
|
| 01/09/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 01/08/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT ELECTRIC INDEPENDENTLY 300.11 ALSO, VDV CABLING INDEPENDENTLY 2. SEAL UNUSED CONDUIT OPENINGS 3. SUPPORT VDV CABLING AS PER 725.6 4. REMOVE BORDERS TO INSPECT LIGHTS & WALLS 5. FINISH INSTALL LIGHTING - EXITS |