Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T07CM03698
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/01/2008 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 01/31/2008 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED POWER ON ? 2) NEED GFCI RECEPTS AT KITCHEN 3) NEED 1" CLEARANCE AT WATER HEATER B-VENT TO COMBUSTIBLES 4) NEED SEDIMENT TRAP AT WATER HEATER 5) NEED ACCESS TO ROOF FOR INSPECTIONS 6) SEAL WATER CLOSET AT FLOOR 7) NEED ANTI-SIPHON AT ALL EXT. HOSE BIBS 8) RECEPTS SHOWING OPEN GROUNDS 9) BOND GAS LINE |