Permit: T07CM03691

Parcel: 13734001C

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
03/10/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
03/07/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. BOX OVERFILL AT FRONT & OVER COUNTER WORK AREA
2. SUPPORT T-STAT CABLING 725.6

OK TO TILE EXCEPT AS NOTED

*A BOND FOR TEMP POWER WILL BE NEEDED AND ADD 02062 TO PERMIT
03/06/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
INSTALL SEISMIC WIRES ON STEM, EXIT, RECEPTS, ABOVE CEILING
02/04/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) NO INTERMEDIATE ON PERMIT CARD
2) OK WALLS ROUGH