Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T07CM03666
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/06/2007 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* | |
11/01/2007 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND RODS TO BE DRIVEN NEC 250.53 2. INSTALL 2 GROUND RODS AT TRAILER & AT SERVICE NEC 250.56 & 250.32 3. SECURE RISER TO TRAILER 4. DIRECT BURY CABLES TO BE MIN. 24" DEEP NEC 300.5 5. INSTALL EQUIPMENT GROUNDING CONDUCTOR FROM SERVICE TO TRAILER - NEC 250.32 6. COMPLETE ALL WORK 7. LABEL ALL BREAKERS AS TO WHAT THEY FEED 8. WIRES TO BE PROTECTED WHERE ENTERING PVC FROM UNDERGROUND 300.5(H) 9. INSTALL CONDUCTORS IN SCHEDULE 80 PVC - NEC 300.5 (D)(4) 10. CONDUCTORS #4 & LARGER TO BE PROTECTED BY BUSHING - NEC 300.4 & 352.46 11. RECALL WHEN READY 12. PROVIDE WARNING RIBBON FOR SERVICE CONDUCTORS NEC 300.5 13. OVERCURRENT PROTECTION FOR CONDUCTORS TO BE PROVIDED AT SOURCE & SIZED ACCORDINGLY - NEC 240.21 & 240.4 |