Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T07CM03664
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/09/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
02/27/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
01/23/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
01/22/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* PROVIDE FITTING ON MINI-SPLIT CONDENSATE PROVIDE DISCONNECT OK FOR CEILING TILES REMAINDER OF PROJECT |
|
12/04/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING TILES 176, 175, 172, 173, 178 |
|
11/06/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
09/23/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK FOR CEILING TILES 2ND FLOOR ROOMS 206, 208, 209, 210, 215-219 CONDENSATE IN WALL 2ND FLOOR OK TO COVER |
|
08/06/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK FOR CEILING TILES PHASE 1 ROOMS 118-124 2) SEE ENGINEER FOR APPROVED LOCATION FOR CONDENSATE TERMINATIONS AND EXPOSED COMBUSTIBLES IN RETURN PLENIUM 3) PROVIDE PERMITS AND INSPECTIONS FOR ALL UNIT REPLACEMENTS |