Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03655
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/29/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
10/26/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR 200.7 2. USE TERMINAL ENDS WITH STRANDED CONDUCTORS 3. CIRCUIT DIRECTORY TO BE AS PER 408.4 - NO ABBREVIATIONS & DISTINGUISHABLE FROM ONE ANOTHER AND CORRECTLY TO WHAT SERVICED 4. AREA AROUND BOX RINGS TO BE NO MORE THAN 1/8" 314.21 5. CLEAN EXCESS PAINT FROM DEVICE TERMINALS 110.12 6. EM/EXIT LIGHTING TO BE AS PER 700.12 |