Permit: T07CM03655

Parcel: 13355231A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03655

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/29/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/26/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR 200.7
2. USE TERMINAL ENDS WITH STRANDED CONDUCTORS
3. CIRCUIT DIRECTORY TO BE AS PER 408.4 - NO ABBREVIATIONS & DISTINGUISHABLE FROM ONE ANOTHER AND CORRECTLY TO WHAT SERVICED
4. AREA AROUND BOX RINGS TO BE NO MORE THAN 1/8" 314.21
5. CLEAN EXCESS PAINT FROM DEVICE TERMINALS 110.12
6. EM/EXIT LIGHTING TO BE AS PER 700.12