Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/24/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 10/22/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION ITEMS #1, #2 AND #4 SECURE TRACK LIGHTING TO STRUCTURE ABOVE WITH 12 GAUGE TIE WIRES CANNOT USE CEILING SUPPORT WIRES FOR ATTACHMENT OF MC CABLE. TIE WIRES INSTALLED FOR SUPPORT MUST BE ATTACHED OF BOTH ENDS. ATTACH TIE WIRES TO JUNCTION BOXES FOR TRACK LIGHT. |
|
| 10/18/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TRUCK LIGHTING TO BE ATTACHED TO STRUCTURE ABOVE CEILING. NOT JUST ATTACHED TO CEILING GRID 2) CANNOT USE CEILING SUPPORT WIRES FOR ATTACHMENT AT MC CABLE. MUST INSTALL SEPERATE SUPPORT WIRES. NEC 300.11 3) SECURE RECESSED FIXTURES TO CEILING GRID 4) RECESSED FIXTURES, ELECTRIC BOXES, ETC IN CEILING TO HAVE #12 WIRE TO BLDG STRUCTURE ABOVE |
|
| 10/09/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 10/08/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |