Permit: T07CM03648

Parcel: 116180260

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
12/20/2007 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
12/14/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NAILING ON BWP S.E. CORNER NOT COMPLETE
2) H.D. AT DINING ROOM WINDOW, NEEDS TO BE CONNECTED TO A DBL STUD NOT A STUD/TRIMMEL
3) MISSING ANCHOR BOLTS ON BRACED PANEL WALLS
4) NEED A LADDER TO ACCESS ROOF
5) RE-NAIL OR STAPLE OSB, WHERE STAPLES HABE BEEN SHOT WITH TO MUCH PRESSURE AND 1/2 WAY THRU OSB