Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T07CM03634
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/10/2007 | PLUMBING - GAS PRESSURE TEST | Approved | ||
09/27/2007 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
09/26/2007 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* - JIM FROM MAINT. - 3 1/2" REQUIRED FOR PIPING ABOVE ROOF, DO NOT STRAIN PIPING. - SUPPORT AT END OF RUNS, CHANGES OF DIRECTION AND NOT TO EXCEED 8' - SUPPORTS NOT PER SPEC. FILE ANY SHARP BURRS FROM STRUT - NATURAL GAS PIPING CONNECTION TO PROPANE PIPING AT GENERATOR NOT PER PLAN |