Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T07CM03626
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/20/2008 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
05/14/2008 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
05/12/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* TESTED 6 DUCT SMOKE DETECTORS 4 AT DELI AREA 1 AT OFFICE AREA 1 AT PHARMACY AREA ALL TESTS OK |
|
05/09/2008 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
05/08/2008 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
05/06/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* D8-R & D8-L 1ST LAYER FIRE WRAP OK |
|
05/02/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* D-70 SECOND LAYER FIRE WRAP OK D-8R 1ST LAYER FIRE WRAP OK T-23 1ST LAYER FIRE WRAP OK D-8L WELD TEST OK |
|
04/29/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* T-23, D8R -- OK WELD INSP. D70 -- OK 1ST LAYER |
|
04/25/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1ST LAYER OF FIRE WRAP MUST BE SECURED TIGHT WITH BANDING OR FILAMENT TAPE AS PER INSTALL INSTRUCTIONS WELDS ON GREASE DUCT LEAKING |
|
04/24/2008 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
04/23/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* EF-6 LEAK TEST OK |
|
04/22/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* BAKERY DUCT OK TO WRAP |
|
04/16/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SECOND LAYER GREASE DUCT WRAP OK METAL BEHIND HOOD OK |
|
04/14/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1ST LAYER ON 1ST 6' OF DROPS OF GREASE DUCT OK PROVIDE PROPER METAL BACKING BEHIND HOOD |
|
04/02/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DINING AREA OK KITCHEN UNIT #3 OK TO WRAP PHARMACY OK TO WRAP LIGHT TEST GREASE DUCT X4 OK ON 6' DROPS |
|
03/26/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DINING AREA: 3 SCREWS IN STRAPS, COMPLETE RETURN DUCTING PHARMACY: COMPLETE DUCT AND EXHAUST AT RESTROOM |
|
03/14/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RETURN DUCT BACK OF SALES AREA OK TO WRAP |
|
03/04/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO WRAP RETURN IN MEZZANINE AREA |