Permit: T07CM03626

Parcel: 140122180


Addresses:

2000 E IRVINGTON RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM03626

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/20/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/19/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. EQUIP. DROPS NOT IN YET
2. A REINSPECTION FEE MAY BE ASSESSED IF NOT READY
FOR INSP.
05/16/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK PHARMACY
05/15/2008 ELECTRIC - INTERMEDIATE Partial Approval OK AREAS EXCEPT MEAT DEPT., TORTILLERIA, BAKERY, DELI, PHARMACY, MECH. ROOM
05/13/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK XFORMER RELOCATE FROM ATTIC ABOVE BAKERY TO BOTTOM FLOOR LEVEL
- OK MAKE UP AIR & EXH. FANS ON ROOF FOR BAKERY
AND DELI
05/09/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SUPPORT CONDUIT DROPS FOR FOOD CASES ABOVE CEILING, EXPOSED SPLICES, CLOSE OPEN J-BOXES
2. FA STROBES NEED SEISMIC TO SUPPORT BOX ON GRID

RETURN UNSCHEDULED INSP. $150.00 CK.#777314691
OK ABOVE CEILING & TCO FOR STOCKING MAIN SALES
05/08/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK FOOD CASES MAIN SALES FLOOR & EM LTG. IN MAIN FLOOR
05/07/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK AC UNITS ON ROOF
05/06/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
INSTALL BOND BUSHINGS ON KO'S WITH CONCENTRIC
OVER 150V TO GROUND PER 250 NEC
OK FOOD CASES
SUPPORT CONDUIT ON ROOF
05/02/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK PANEL "M" AND FEEDER
04/30/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK XFORMER "TC" & PANEL "TR" ALSO "CFA" & "CFB"
- OK NEW COOLING TOWER
04/28/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/25/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. 75KVA XFMR CANNOT BE LOCATED ABOVE CEILING
NEC 450.13(B)
2. NEED PROPER WORKING CLEARANCE @ PANELS IN SWITCHGEAR ROOM
3. NEED PROPER WORKING CLEARANCE @ 75KVA XFMR
4. PANEL HA FEED GOES THROUGH SERVICE SECTION OF SWITCH GEAR
5. NEED PROTECTIVE BUSHING FOR CONDUCTORS #4 OR LARGER
6. OK PANELS BDA, PA, CL, PH, DPA, DPB, L
04/23/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK PANEL "HA"
04/22/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK CEILINGS PHARMACY & PRODUCE AREA
REMOVE TEMP LIGHTING
04/18/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK HARD LID ABOVE MEAT COUNTER
04/17/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEE NOTES LAST INSP.
SUPPORT CONDUITS PER CODE
04/16/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL ROUGH, MEAT DEPT.
04/09/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK BAKERY, CHECK CASHING WALLS
04/08/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS IN TORTILLERIA, DELI, BAKERY

CONDUITS ABOVE PANEL BOARDS NOT APPROVED
PER NEC 90.4, 110.3, 300.11, 358 -- OK PHARMACY
04/04/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK OUTSIDE WALL TORTILLERIA AREA
2. OK LOW WALL TORTILLERIA AREA
3. OK OUTSIDE EAST WALL DELI
03/20/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK PVC U.G PRE-SLAB EAST SIDE OF BUILDING
03/13/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS @ PHARMACY, CUSTOMER SERVICE AND MANAGERS OFFICE AND SAFE ROOM
03/12/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. STRAP CONDUIT WITHIN 3' OF TERMINATION AS PER NEC
2. 1 HOLE STRAPS MUST BE FLAT ON SURFACE OR STRUCTURE
03/07/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK UNDER SLAB CONDUITS FOR MEAT TABLES
02/29/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK UNDER SLAB BRANCH CIRCUIT IN PHARMACY & ROUGH FOR WATER FOUNTAIN S.W CORNER
02/26/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK UNDER SLAB FOR REFRIG. CASES ON NORTHWEST CORNER