Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM03626
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/20/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
05/19/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. EQUIP. DROPS NOT IN YET 2. A REINSPECTION FEE MAY BE ASSESSED IF NOT READY FOR INSP. |
|
05/16/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK PHARMACY |
|
05/15/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | OK AREAS EXCEPT MEAT DEPT., TORTILLERIA, BAKERY, DELI, PHARMACY, MECH. ROOM | |
05/13/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK XFORMER RELOCATE FROM ATTIC ABOVE BAKERY TO BOTTOM FLOOR LEVEL - OK MAKE UP AIR & EXH. FANS ON ROOF FOR BAKERY AND DELI |
|
05/09/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SUPPORT CONDUIT DROPS FOR FOOD CASES ABOVE CEILING, EXPOSED SPLICES, CLOSE OPEN J-BOXES 2. FA STROBES NEED SEISMIC TO SUPPORT BOX ON GRID RETURN UNSCHEDULED INSP. $150.00 CK.#777314691 OK ABOVE CEILING & TCO FOR STOCKING MAIN SALES |
|
05/08/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK FOOD CASES MAIN SALES FLOOR & EM LTG. IN MAIN FLOOR |
|
05/07/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK AC UNITS ON ROOF |
|
05/06/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* INSTALL BOND BUSHINGS ON KO'S WITH CONCENTRIC OVER 150V TO GROUND PER 250 NEC OK FOOD CASES SUPPORT CONDUIT ON ROOF |
|
05/02/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK PANEL "M" AND FEEDER |
|
04/30/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK XFORMER "TC" & PANEL "TR" ALSO "CFA" & "CFB" - OK NEW COOLING TOWER |
|
04/28/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
04/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. 75KVA XFMR CANNOT BE LOCATED ABOVE CEILING NEC 450.13(B) 2. NEED PROPER WORKING CLEARANCE @ PANELS IN SWITCHGEAR ROOM 3. NEED PROPER WORKING CLEARANCE @ 75KVA XFMR 4. PANEL HA FEED GOES THROUGH SERVICE SECTION OF SWITCH GEAR 5. NEED PROTECTIVE BUSHING FOR CONDUCTORS #4 OR LARGER 6. OK PANELS BDA, PA, CL, PH, DPA, DPB, L |
|
04/23/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK PANEL "HA" |
|
04/22/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CEILINGS PHARMACY & PRODUCE AREA REMOVE TEMP LIGHTING |
|
04/18/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK HARD LID ABOVE MEAT COUNTER |
|
04/17/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE NOTES LAST INSP. SUPPORT CONDUITS PER CODE |
|
04/16/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL ROUGH, MEAT DEPT. |
|
04/09/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK BAKERY, CHECK CASHING WALLS |
|
04/08/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS IN TORTILLERIA, DELI, BAKERY CONDUITS ABOVE PANEL BOARDS NOT APPROVED PER NEC 90.4, 110.3, 300.11, 358 -- OK PHARMACY |
|
04/04/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK OUTSIDE WALL TORTILLERIA AREA 2. OK LOW WALL TORTILLERIA AREA 3. OK OUTSIDE EAST WALL DELI |
|
03/20/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK PVC U.G PRE-SLAB EAST SIDE OF BUILDING |
|
03/13/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS @ PHARMACY, CUSTOMER SERVICE AND MANAGERS OFFICE AND SAFE ROOM |
|
03/12/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. STRAP CONDUIT WITHIN 3' OF TERMINATION AS PER NEC 2. 1 HOLE STRAPS MUST BE FLAT ON SURFACE OR STRUCTURE |
|
03/07/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK UNDER SLAB CONDUITS FOR MEAT TABLES |
|
02/29/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK UNDER SLAB BRANCH CIRCUIT IN PHARMACY & ROUGH FOR WATER FOUNTAIN S.W CORNER |
|
02/26/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK UNDER SLAB FOR REFRIG. CASES ON NORTHWEST CORNER |