Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T07CM03626
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/12/2008 | FRAMING | Approved | IVRS - Inspection :* | |
05/02/2008 | FRAMING | Partial Approval | IVRS - Inspection :* NEED CALCULATIONS FOR TRANSFORMER MEZZ/DECK AND DETAIL |
|
04/30/2008 | FRAMING | Partial Approval | IVRS - Inspection :* ADD 2 X 12's TO MEZZANINE |
|
04/24/2008 | FRAMING | Not ready for Inspection | IVRS - Inspection :* PLEASE ADD 01036 PARTIAL PHARMACY & PRODUCE |
|
04/23/2008 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
04/15/2008 | FRAMING | Partial Approval | IVRS - Inspection :* NEED APPROVED/REVISED PLANS WITH DETAILS |
|
04/12/2008 | FRAMING | Not ready for Inspection | IVRS - Inspection :* NEEDS SLIP TRACK AND CONTINUOUS BLOCKING AT CEILING |
|
04/10/2008 | FRAMING | Partial Approval | IVRS - Inspection :* BREAK AREA 6X12 BEAMS SECURE OK TO ROCK EXTERIOR WALL |
|
04/08/2008 | FRAMING | Partial Approval | IVRS - Inspection :* NEED DETAIL FOR MEAT COMPARTMENT SOFFIT PARTIAL WALL BETWEEN LOADING DOCK AND TORTILLERIA ROOM NEEDS TO GO TO DECK |
|
04/03/2008 | FRAMING | Not ready for Inspection | IVRS - Inspection :* NEEDS DETAIL FOR JOIST TO WALL CONNECTIONS AT S3(2) |
|
03/27/2008 | FRAMING | Not ready for Inspection | IVRS - Inspection :* DETAILS 7 & 2 A-11 |
|
03/26/2008 | FRAMING | Partial Approval | IVRS - Inspection :* MECH. UNIT SUPPORT FOR PHARMACY OK PHARMACY BATH OK NEEDS RFI FOR PHARMACY |
|
03/18/2008 | FRAMING | Not ready for Inspection | IVRS - Inspection :* NEED RFI FULL HEIGHT WALL |
|
03/17/2008 | FRAMING | Partial Approval | IVRS - Inspection :* FRAMING OK AT - PRODUCE, CHECK CASHING, BOOKKEEPING AND MONEY ROOM REMODELS |
|
03/12/2008 | FRAMING | Not ready for Inspection | IVRS - Inspection :* DETAIL 6 & 10 ON ALL ADA BACKING RESTROOMS FRAMING FOR HARD LID |
|
03/04/2008 | FRAMING | Partial Approval | IVRS - Inspection :* BLOCKING FOR SCREEN WALL LINE D 4 UNITS LINE H 4 UNITS AC UNITS AT E,F,G,H HOOD #350, #275, #300 NEEDS REVISED PLANS FOR NEW WALL AND FOOTING UNDER MEZZANINE |