Permit: T07CM03623

Parcel: 125043310


Addresses:

2424 E HAWTHORNE ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/17/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/18/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REVISE PANEL DIRECTORY TO SHOW ADDITION OF PN CKT AND ALTERATIONS OF CKT'S (TWIN BREAKERS) TO MAKE ROOM FOR PN BREAKER - MAKE SURE THEY ARE CORRECTLY IDENTIFIED
2. ALTERED CKTS WITH SHARED NEUTRALS TO TERMINATE ON SEPARATE PHASES
3. TWO #8 STRANDED NOT TO BE UNDER SAME SCREW IN METER BASE
4. NEED SEALING TYPE LOCKNUT, SIDE ENTRY INTO METER BASE
5. PROVIDE PROPER WRENCH TO OPEN INVERTER

PARTIAL INSPECTION