Permit: T07CM03616

Parcel: 133180450


Addresses:

7052 E 2ND ST

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
11/23/2007 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
11/06/2007 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FOOTINGS MUST BE A MINIMUM OF 12" WIDE AT BOTTOM
2) REINFORCING STEEL MUST BE AT LEAST 3" FROM SOIL
3) VERTICAL REBAR SUPPORTING HORIZONTAL MUST BE ISOLATED (PLASTIC TAPE) FROM HORIZONAL STEEL TO KEEP RUST FROM HORIZONTAL STEEL