Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/05/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK ROOF OK PREVIOUS ITEMS EXCEPT EM LIGHTING FOR EGRESS |
|
| 12/04/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. FIXTURES TO BE SECURELY ATTACHED TO GRID 410.16 2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20 3. MAINTAIN WORKING CLEARANCE AT AC DISCONNECT 110.26 4. SUPPORT MC CABLE AS PER CODE 330.30 5. SUPPORT VDV CABLING 725.6, 800.6, 300.11 6. A DISCONNECTING MEANS IS NEEDED FOR WATER HEATER 7. LABEL PANEL DIRECTORY 408.4 - NO ABBREVIATIONS 8. SECURE FITTING TO FIXTURE 9. 2 EXIT LIGHTS NOT WORKING ALSO, NIGHT LIGHTS ON EM PACKS 10. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS |