Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/06/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/05/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK ROOF
OK PREVIOUS ITEMS
EXCEPT EM LIGHTING FOR EGRESS
12/04/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. FIXTURES TO BE SECURELY ATTACHED TO GRID 410.16
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
3. MAINTAIN WORKING CLEARANCE AT AC DISCONNECT 110.26
4. SUPPORT MC CABLE AS PER CODE 330.30
5. SUPPORT VDV CABLING 725.6, 800.6, 300.11
6. A DISCONNECTING MEANS IS NEEDED FOR WATER HEATER
7. LABEL PANEL DIRECTORY 408.4 - NO ABBREVIATIONS
8. SECURE FITTING TO FIXTURE
9. 2 EXIT LIGHTS NOT WORKING ALSO, NIGHT LIGHTS ON
EM PACKS
10. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS