Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
12/06/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/20/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS
RECEIVED LETTER FOR FITTINGS
11/19/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) TIGHTEN LOOSE FITTINGS
2) SUPPORT M/C CABLES WITHIN 12" OF BOXES
3) MAINTAIN DEDICATED SPACE ABOVE PANEL 110.26
4) PLANS CALL FOR COMPRESSION FITTINGS WITH CONDUIT/EMT
11/16/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELLED BY DEAN
10/31/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*