Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/20/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS RECEIVED LETTER FOR FITTINGS |
|
| 11/19/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) TIGHTEN LOOSE FITTINGS 2) SUPPORT M/C CABLES WITHIN 12" OF BOXES 3) MAINTAIN DEDICATED SPACE ABOVE PANEL 110.26 4) PLANS CALL FOR COMPRESSION FITTINGS WITH CONDUIT/EMT |
|
| 11/16/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY DEAN |
|
| 10/31/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |