Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03603
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/30/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/23/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH #4 & #5 |
|
01/22/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SUPPORT VDV CABLING PER 725.6, 800.6 2. IDENTIFY CONDUCTORS AT LUGS 3. USE CORRECT COLOR FOR GROUNDING EQUIPMENT CONDUCTOR -- 250.119 4. LABEL BREAKERS DISTINGUISHABLE FROM ONE ANOTHER -- 408.4 5. DERATE CONDUCTOR PER 310.15 PANEL "HB" 6. LABEL OUTSIDE PANELS PER 210.5 7. GROUND JUNCTION BOX 8. NEED ARC FLASH LABELING |
|
12/21/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20 2) INSTALL DOOR BELL SYSTEM PER PLANS 3) OPEN AREAS OF CEILING TO INSEPCT VDV CABLES INSTALLED AFTER LAST INSPECTION 4) WAITING ON PLAN REVISIONS FOR SPLIT SYSTEM 5) CHECK SERVICE |