Permit: T07CM03602

Parcel: 122180660


Addresses:

3618 E PIMA ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
03/13/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. BOND REBAR @ POLE BASES WITH DIRECT BURIAL CLAMPS
2. CONCRETE ENCASE PVC WHERE LESS THAN 18"

OK TO COVER TRENCHES AND POUR POLE BASES (2) AFTER CORRECTIONS.