Permit: T07CM03599

Parcel: 13018077A


Addresses:

2020 S COLUMBUS BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03599

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/15/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/10/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUND ALL METAL BOXES
2. RE-IDENTIFY WHITE WIRES USED AS PHASE CONDUCTORS
3. INSTALL SERVICE RECEPT FOR AIR HANDLER & CONDENSING UNIT
4. NEED TO SUPPORT SECURE EMT ON ROOF
5. AC DISCONNECT CANNOT BE MOUNTED ON SERVICE PANEL
6. LIGHT FOR ATTIC SPACE TO BE TURNED ON @ SCUTTLE HOLE
7. USE ROMEX CONNECTOR ON CABLE TO AIR HANDLER
8. CLOSE OPEN KNOCKOUTS IN PANELS
9. HAVE SINGLE PHASE 120/240V SYSTEM WIRE ACCORDINGLY
10. ONE NEUTRAL PER TERMINAL @ PANELS
11. AIR HANDLER DOES NOT HAVE PROPER OVERCURRENT PROTECTION
12. INSTALL EXTENSIONS ON BOXES MORE THAN 1/4" BACK
13. CANNOT HAVE MORE THAN 1/8" GAP AROUND MUD RINGS
14. HAVE ELECTRICIAN GO THROUGH ENTIRE JOB
INSTALL PER CODE & PLANS