Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03599
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/15/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/10/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND ALL METAL BOXES 2. RE-IDENTIFY WHITE WIRES USED AS PHASE CONDUCTORS 3. INSTALL SERVICE RECEPT FOR AIR HANDLER & CONDENSING UNIT 4. NEED TO SUPPORT SECURE EMT ON ROOF 5. AC DISCONNECT CANNOT BE MOUNTED ON SERVICE PANEL 6. LIGHT FOR ATTIC SPACE TO BE TURNED ON @ SCUTTLE HOLE 7. USE ROMEX CONNECTOR ON CABLE TO AIR HANDLER 8. CLOSE OPEN KNOCKOUTS IN PANELS 9. HAVE SINGLE PHASE 120/240V SYSTEM WIRE ACCORDINGLY 10. ONE NEUTRAL PER TERMINAL @ PANELS 11. AIR HANDLER DOES NOT HAVE PROPER OVERCURRENT PROTECTION 12. INSTALL EXTENSIONS ON BOXES MORE THAN 1/4" BACK 13. CANNOT HAVE MORE THAN 1/8" GAP AROUND MUD RINGS 14. HAVE ELECTRICIAN GO THROUGH ENTIRE JOB INSTALL PER CODE & PLANS |