Permit: T07CM03576

Parcel: 137055220

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03576

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/05/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/04/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
10/02/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTES
SWITCH BOXES P-RINGS TO SHORT - PROPERLY EXTEND TO FLUSH WITH DRYWALL PER NEC
09/27/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
09/25/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
- MC CABLE MUST BE SUPPORTED TO STRUCTURE NOT TO EACH OTHER, DO NOT USE CEILING WIRES INTENDED TO SUPPORT GRID, WHEN USING YOUR OWN WIRES TO SUPPORT CABLING THEY MUST BE TIED OFF AT TOP & BOTTOM
PER 300 NEC