Permit: T07CM03576

Parcel: 137055220

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM03576

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
09/27/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
09/25/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/21/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MC CABLE TO CLOSE TO FACE OF STUD MUST
HAVE 1 1/4" MIN. CLEARANCE TO PROTECT FROM SCREWS
PER NEC
2. SUPPORT MC WITHIN 12" OF TERMINATIONS & AT 6' INTERVALS PER NEC CABLES, DATA TO BE SUPPORTED TO STRUCTURE. CEILING GRID WIRES ARE NOT TO BE USED TO SUPPORT WIRING, RACEWAYS WHEN USING WIRES TO TIE OR SUPPORT, THEY MUST BE TIED OFF AT BOTH ENDS