Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM03573
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/27/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/07/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR SERVICE 1. SERVICE SECONDARY COVER BEFORE INSPECTION 2. NEED WARNING RIBBON MIN. 12" ABOVE SERVICE RACEWAYS 3. PROVIDE LISTING FOR SECONDARY RACEWAY 4. BOND SERVICE RISER 5. TIGHTEN ALL CONNECTIONS 6. IDENTIFY ALL SERVICE DISCONNECTS AS SUCH 7. BOND NIPPLES INSPECTION STOPPED CORRECT AS DISCUSSED ADD CABLE DROP TO PERMIT |
|
| 02/15/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL & CEILING COVER |