Permit: T07CM03559

Parcel: 128100540

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03559

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/30/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/29/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. NEED TO SEE CONNECTIONS OF OFFICE FURNITURE. IF AFTER THIS PROJECT A SEPERATE PERMIT FOR ELECTRIC WILL BE NEEDED
2. PANEL SCHEDULE TO BE AS PER 408.4 -
NO ABBREVIATIONS & DISTINGUISHABLE FROM ONE ANOTHER
3. DERATE CONDUCTORS PER 310.15
4. INSTALL ALL STRANDS UNDER LUG
5. INSTALL GROUNDING ELECTRODE PER 250.64
6. BOND GROUNDED TERMINAL AT TRANSFORMER
7. NO MORE THAN 360 DEG. IN A CONDUIT RUN