Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM03544
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/18/2009 | ELECTRIC - INTERMEDIATE | Approved | ||
02/17/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
02/13/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
12/22/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUNDING ELECTRODE SYSTEM DOES NOT MEET REQUIREMENTS OF UFER. NEC 250.52 NEED TO INSTALL GROUND RODS 2. WIRING IN RAMADAS TO BE INSTALLED IN RECOGNIZED WIRING METHOD OF CHAPTER 3 OF NEC 300.3(A) OF NEC 3. HAVE MORE THAN ONE BRANCH CIRCUIT TO SEPARATE STRUCTURES SEE NEC 225.30 4. NEED DISCONNECTING MEANS @ EACH STRUCTURE SERVED SEE NEC 225.31, 225.32 5. NEED GROUNDING ELECTRODE SYSTEM @ EACH STRUCTURE SEE NEC 250.32 |
|
10/29/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELED BY CONTRACTOR |
|
10/01/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 1ST LIFT WALL A AMPHITHEATER |