Permit: T07CM03534

Parcel: 10309064B

Inspection Status: Not ready for Inspection

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/30/2007 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
PROVIDE BALANCE REPORT
SET UP FOR SMOKE TEST
11/30/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
- ALL DUCT DETECTORS OK
- PROVIDE UPDATED EQUIPMENT SCHEDULE
REFLECTING HEAT STRIP CHANGE
11/15/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
TRAINING ROOM 403 OK TO INSTALL CEILING TILE
HALLWAY 410 OK TO INSTALL CEILING TILE
ROOM 400 OK TO INSTALL CEILING TILE
10/29/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
FLASHING ON RTU-38 NEEDS REPAIR
C.U. UNIT ON ROOF OVERFUSED
PROVIDE DUCT DETECTOR COMPLETION
FIRE MARSHALL OK TO TEST