Permit: T07CM03534

Parcel: 10309064B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/11/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/03/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
11/30/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
PARTIAL INSPECTION
1. IF HEAT STRIPS ARE TO BE DELETED, REVISE PLANS TO REFLECT THAT
2. PANEL DIRECTORIES TO BE MORE ACCURATE/IDENTIFY AREAS/ROOMS - NEC 408.4

OK TO OCCUPY ROOM 402
11/29/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
11/19/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
11/16/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
10/30/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. NEED DISCONNECT FOR FURNITURE - USE 605.6
2. BOND FOR X-FORMER TO DISCONNECT L6
UNDERSIZED 250.30 A3 (AND LB)
3. NEED UPSIZED #10 NEUTRAL PER NOTE #11
10/29/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION

INSPECTION FOR ROOFTOP
1. STRAP FLEX WITHIN 12" OF ENCLOSURES
2. RTU 38 2 GROUNDS UNDER LUG IN DISCONNECT
3. IDENTIFY PHASE CONDUCTORS AT TERMINATIONS
4. PLANS SHOW AUX. HEAT STRIPS IN RTU'S
5. DISCONNECT RTU #35 NOT GROUNDED
6. NEED SERVICE RECEPTACLE WITHIN 25' OF RTU'S
7. TAPS NOT TO BE OVER 25' PER NEC 240.21
8. EQUIPMENT GROUNDS TO J-BOXES NOT SIZED PROPERLY
9. NEED TO FOLLOW PLANS NOTES FOR ALL BRANCH CKT WIRING
10. FINISH ALL WIRING