Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM03534
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/11/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
11/19/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK INTERIOR OF TRAINING ROOM AND LOBBY ROOM 403 MULTI WIRE BRANCH CKT TO WIRE MOLD TO BE COM. TRIP 210.4 |
|
11/16/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
11/15/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TILES (CEILING) TRAINING ROOM LOBBY |
|
10/30/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
10/29/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
10/25/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* CEILING INSPECTION WILL BE MADE WHEN THIS AREA WILL BE READY FOR FINAL INSPECTION FOR OCCUPANCY |
|
10/10/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
10/04/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) COMPLETE FIXTURE WIRING-BE ADVISED THAT LV CABELING MUST BE OFF GRID, INSTALLED PER 725-800 NEC |