Permit: T07CM03526

Parcel: 13316024M

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/04/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/31/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE - 314.20
2. PANEL SCHEDULE TO BE AS PER 408.4 - NO ABBREVIATIONS AND DISTINGUISHABLE FROM ONE ANOTHER
3. TIGHTEN DEVICES TO WALL