Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/04/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/31/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE - 314.20 2. PANEL SCHEDULE TO BE AS PER 408.4 - NO ABBREVIATIONS AND DISTINGUISHABLE FROM ONE ANOTHER 3. TIGHTEN DEVICES TO WALL |