Permit: T07CM03519

Parcel: 13502134B


Addresses:

6970 E 22ND ST #118

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
01/03/2008 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
WATER TEST THRU ROOF OK
WATER PIPING OK
01/02/2008 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MIN. TRAP ARM DISTANCE IS 2X PIPE DIAM. (6")
2. 3" CLEAN OUT REQUIRED ON SINK
12/31/2007 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOT PER PLAN
BACK PITCH
MISSION COUPLINGS REQUIRED
WRAP PIPING WATER PASSING THROUGH CONCRETE