Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2008 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* WATER TEST THRU ROOF OK WATER PIPING OK |
|
| 01/02/2008 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MIN. TRAP ARM DISTANCE IS 2X PIPE DIAM. (6") 2. 3" CLEAN OUT REQUIRED ON SINK |
|