Permit: T07CM03508

Parcel: 130171530


Addresses:

4052 E SYLVANE DR

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
02/07/2008 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
02/05/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NAIL OFF PARAPET OSB ON BACK (SOUTH) WALL OF GARAGE
2. NAIL OFF OSB EAST OF ENTRY DOOR
3. OPEN MIDDLE COLUMN OSB FOR INSPECTION WHEN PLANS ARE PRESENT
4. MARK NEW ELEC. PANEL WITH ADDRESS
5. LABEL NEW SUB-PANEL BREAKERS
6. NEED PLANS & PERMIT TO PASS SERVICE UPGRADE
02/04/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO PLANS OR PERMIT ON SITE
2) KNOCKED-NO ONE PRESENT 8:05 AM
3) LEFT MESSAGE ON PHONE AT 7:25 AM
4) PLEASE RECALL
01/30/2008 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) 5 1/8" BEAM NOT INSTALLED YET ROOF SUPPORT
2) E.3508.3 IRC GROUND RODS 6'-0" APART
3) USE NON METALIC CONDUIT SCHEDULE 80 FROM GROUND TO RISER
4) USE ONLY SQUARE "D" BREAKERS
5) BOND GROUND BUSS AT SUB PANEL
6) SUPPORT PARAPETS WITH WING WALLS