Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2008 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 02/05/2008 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NAIL OFF PARAPET OSB ON BACK (SOUTH) WALL OF GARAGE 2. NAIL OFF OSB EAST OF ENTRY DOOR 3. OPEN MIDDLE COLUMN OSB FOR INSPECTION WHEN PLANS ARE PRESENT 4. MARK NEW ELEC. PANEL WITH ADDRESS 5. LABEL NEW SUB-PANEL BREAKERS 6. NEED PLANS & PERMIT TO PASS SERVICE UPGRADE |
|
| 02/04/2008 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO PLANS OR PERMIT ON SITE 2) KNOCKED-NO ONE PRESENT 8:05 AM 3) LEFT MESSAGE ON PHONE AT 7:25 AM 4) PLEASE RECALL |
|
| 01/30/2008 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) 5 1/8" BEAM NOT INSTALLED YET ROOF SUPPORT 2) E.3508.3 IRC GROUND RODS 6'-0" APART 3) USE NON METALIC CONDUIT SCHEDULE 80 FROM GROUND TO RISER 4) USE ONLY SQUARE "D" BREAKERS 5) BOND GROUND BUSS AT SUB PANEL 6) SUPPORT PARAPETS WITH WING WALLS |