Permit: T07CM03501

Parcel: 12409159A


Addresses:

1801 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM03501

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/03/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
02/19/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WIRING TO BE PER APPROVED PLAN
OK TO INSTALL N.W OFFICE CABINET
02/15/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
10/31/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK FLOOR & METAL BOXES
10/26/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ROMEX TO BE CONNECTED TO METAL BOXES WITH ROMEX CONNECTOR
2. FLOOR BOXES NOT CORRECT YET
3. ROMEX IS NOT TO BE STAPLED ON SIDE

CALL AGAIN WHEN PROPER FLOOR BOXES IN
10/18/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
STILL NEED TO COMPLETE CORRECTIONS #1,3,9 FROM PREVIOUS INSPECTION -- OK WALL & CEILING COVER
10/12/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. WIRING NOT PER PLAN
2. ROMEX TO BE PROPERLY SECURED/SUPPPORTED IN CRAWL SPACE
3. FLOOR BOXES ARE FOR RACEWAY ENTRY, NOT ROMEX
4. CEILING CANS TO BE SECURED TO STRUCTURE
5. BOXES NOT TO BE MOUNTED WITH SCREWS ON THE INTERIOR OF BOX
6. ROMEX TO BE STAPLED WITHIN 12" OF BOXES/CAN LIGHTS
7. INSTALL NAIL PLATES AS NEEDED
8. ROMEX TO BE RAN IN A NEAT AND WORKMANLIKE MANNER
9. OLD/UNUSED WIRING TO BE REMOVED WHERE ACCESSIBLE