Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03500
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/07/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
02/06/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* WORK NOT COMPLETE RENE 850-4632 |
|
02/05/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. AC SERVICE GFI NOT WORKING, NOT SERVICE TO WALL 2. PROVIDE DISCONNECTING MEANS FOR INSTA-HOT NEC 422.31B 3. PROVIDE PROPER COVERS FOR FLOOR RECEPTACLES 4. FURNACE HAS WRONG SIZE FUSES 5. PROVIDE 20 AMP CKT'S TO INSTA-HOT'S FINISH ALL PREVIOUS CORRECTIONS NEED TO PAY REINSPECTION FEE 6. PANEL DIRECTORY TO BE NEAT, LEGIBLE AND CORRECT |
|
02/01/2008 | ELECTRIC - FINAL | Cancelled | CANCELLED PER CONTRACTOR RENE #850-4632 | |
02/01/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
01/31/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FINISH FLOOR TO ACCESS FLOOR BOX PLACEMENT 2. SECURE AC DISCONNECT TO STRUCTURE 3. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 4. TIGHTEN LOOSE FITTINGS 5. GROUND SWITCHES 404.9 6. BOXES MORE THAN 1/4" - 314.20 7. PLEASE VERIFY INSTA-HOT AS A CORD AND PLUG CONNECTED UNIT 8. USE APPROVED EXTENSION BOX 9. MISSING OUTSIDE LIGHTS 10. OUTSIDE GFI NOT WORKING 11. RECESS CANS NOT AS PER PLAN - VERIFY ENGINEER APPROVAL |