Permit: T07CM03500

Parcel: 12409158A


Addresses:

1809 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/07/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/06/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WORK NOT COMPLETE

RENE 850-4632
02/05/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. AC SERVICE GFI NOT WORKING, NOT SERVICE TO WALL
2. PROVIDE DISCONNECTING MEANS FOR INSTA-HOT
NEC 422.31B
3. PROVIDE PROPER COVERS FOR FLOOR RECEPTACLES
4. FURNACE HAS WRONG SIZE FUSES
5. PROVIDE 20 AMP CKT'S TO INSTA-HOT'S
FINISH ALL PREVIOUS CORRECTIONS

NEED TO PAY REINSPECTION FEE

6. PANEL DIRECTORY TO BE NEAT, LEGIBLE AND CORRECT
02/01/2008 ELECTRIC - FINAL Cancelled CANCELLED PER CONTRACTOR RENE #850-4632
02/01/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
01/31/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. FINISH FLOOR TO ACCESS FLOOR BOX PLACEMENT
2. SECURE AC DISCONNECT TO STRUCTURE
3. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS
4. TIGHTEN LOOSE FITTINGS
5. GROUND SWITCHES 404.9
6. BOXES MORE THAN 1/4" - 314.20
7. PLEASE VERIFY INSTA-HOT AS A CORD AND PLUG CONNECTED UNIT
8. USE APPROVED EXTENSION BOX
9. MISSING OUTSIDE LIGHTS
10. OUTSIDE GFI NOT WORKING
11. RECESS CANS NOT AS PER PLAN - VERIFY ENGINEER APPROVAL