Permit: T07CM03497

Parcel: 14029212B

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/27/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/20/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) EXHAUST FANS ARE NOT AS SPECIFIED ON PLANS, FANS ARE RUNNING AT 180 DEGRESS OF DESIGN, PROVIDE ENGINEERS APPROVAL ON UNIT AND CFM CHANGES
2) UNITS OVER FUSED ALL C-UNITS, 50 INSTALLED NEED 45
02/04/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
02/02/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*