Permit: T07CM03497

Parcel: 14029212B

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
06/10/2009 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
LETTER FROM ENGINEER OK TO DELETE DUCT SMOKE DETECTORS - CORRECTIONS HAVE BEEN MADE - OK FOR CEILING TILES
06/03/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) COMPLETE INSULATION OF ALL DUCT ABOVE CEILING, INCLUDING CANS AND SEAL ALL VAPOR BARRIERS
2) DUCT AT S.W. ROOM NOT SEALED
3) PROVIDE FULL RADIUS BENDS AT FLEX
02/10/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/04/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/02/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*