Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/10/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/09/2009 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
| 11/05/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* LAST ITEMS 1) ARC SHIELDS BATHROOMS 2) WATER HEATER 110.26 3) ROOM 150 4) OUTDOOR LIGHTING PAPERWORK |
|
| 11/04/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 11/03/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK ROOF 2) OK RECEPTION COUTNERS 3) BOND LIGHT POLE PER 250.53 4) FINISH ARC SHIELDS |
|
| 11/02/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BOXES MORE THAN 1/4" BOX TO SURFACE IN NON COMBUSTIBLE 314.20 2) WATER FOUNTAIN RECEPTACLE NOT ACCESSIBLE 3) PLEASE VERIFY LISTING FOR FISH TANK HEATERS 4) FINISH FLOOR BOXES 5) MAINTAIN WORKING CLEARANCES AT W/H DISCONNECT 6) LOOKED AT CLASSROOMS ONLY, EXCEPT #150. ALSO AFTER SCHOOL |