Permit: T07CM03497

Parcel: 14029212B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/10/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/09/2009 ELECTRIC - FINAL Cancelled IVRS - RI canceled
11/05/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
LAST ITEMS
1) ARC SHIELDS BATHROOMS
2) WATER HEATER 110.26
3) ROOM 150
4) OUTDOOR LIGHTING PAPERWORK
11/04/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
11/03/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK ROOF
2) OK RECEPTION COUTNERS
3) BOND LIGHT POLE PER 250.53
4) FINISH ARC SHIELDS
11/02/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) BOXES MORE THAN 1/4" BOX TO SURFACE IN NON COMBUSTIBLE 314.20
2) WATER FOUNTAIN RECEPTACLE NOT ACCESSIBLE
3) PLEASE VERIFY LISTING FOR FISH TANK HEATERS
4) FINISH FLOOR BOXES
5) MAINTAIN WORKING CLEARANCES AT W/H DISCONNECT
6) LOOKED AT CLASSROOMS ONLY, EXCEPT #150. ALSO AFTER SCHOOL