Permit: T07CM03497

Parcel: 14029212B

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
11/10/2009 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
07/20/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK ELECTRIC ABOVE CEILINGS ROOMS 120,120A,123,124,125,138,143 & 115
2) FINISH MAKE UP INTERLOCK
07/09/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK BORDER CUTS HALLS
2) FINISH SUPPORTING NOT LAYING ON DUCTS AND PIPES OF VDV CABLES ASLO ATTACH AT BOTH ENDS 300.11
06/25/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
FINISH VDV CABLING
06/15/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. CHECK BOX FILL
2. LABELING FOR METER SWITCHES NOT LEGIBLE -
PAINTED OVER
3. SUPPORT VDV CABLING 725.24, 800.24, 300.11

OK LIGHTS ROOMS 112, 113, 115, 116, 119, 122, 123, 138,
130, 132, 136, 141, 143, 145, 146, 148, 152, 154, 156 - ABOVE CEILING ONLY

DO NOT TILE UNTIL COMPLETE
04/08/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
12/17/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK AC CONDUIT RUNS