Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/10/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/03/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 10/29/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) FOR C OF O OR TEMP C OF O WITHOUT SCOPE OF WORK BEING FINISHED. NEED TO TALK WITH LEE RAY HANLY 909-5154 2) NO ELECTRICAL FINALS HAVE BEEN DONE AT THIS TIME |
|
| 07/30/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 07/23/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) BREAKERS NOT PER REVISED PLANS PER AIC RATINGS 2) NEED A COPY OF HIGH POT TEST 3) OTHER ITEMS CORRECTED AT SERVICE |
|
| 07/09/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 06/29/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) A BOND IS NEEDED FOR POWER 2) ALL DEVICES AND CONDUCTORS TO BE PLUGED, BWITCHED OR PLATED 3) PROTECT CONDUCTOR PER 352.46 AND 300.4 4) PLEASE PROVIDE LETTER OF TORQUE OF EQUIPMENT 5) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM BOTTOM OF PANELS 6) CAP OFF ALL UNUSED CONDCUIT OPENINGS 7) NEED CITY APPROVED PLANS ON SITE ------------------------------------------------------------------------------------------------ ROOF: 1) SUPPORT LFNMC OFF OF ROOF 2) LABEL DISCONNECTS 3) BOND ENCLOSURERS 4) FINISH EXHAUST FANS |
|
| 04/08/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CANS NY VILLAGE AND MEDIA ROOM STRAP CANS WITHIN 12" |
|
| 03/16/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK WALLS ROOMS 128, KITCHEN 121A, 121B, 126 2. OK HARD LIDS 121A & 121B |
|
| 02/18/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK REMAINDER OF WALLS, EXCEPT KITCHEN 2. OK SOFFITS SAFARI ROOM; BATHROOM HARD LIDS |
|
| 02/06/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS #122, 119, 118, 114, 160, 113, 112 |
|
| 01/09/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS BETWEEN COLUMN LINE 5 TO 7 EXCLUDING PRESCHOOL #5 |