Permit: T07CM03496

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03496

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/25/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/23/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOND BUSHING NEEDED AT CONCENTRICS - 250.97
2. BOND DISCONNECT ENCLOSURE - 250
3. USE LUGS LISTED FOR CONDUCTOR SIZED - 110.3
4. FINISH BATHROOM IS INSTA-HOT CORD & PLUG LISTED
5. EXIT/EM LIGHTING TO BE AS PER 700.12
6. MULTIPLE TERMINATIONS AT TRANSFORMER GROUNDED TERMINAL - 110.14
7. PLEASE PROVIDE LABLEING AS PER #12 OF SPECS OR REVISE SPECS
8. GROUND CONDUCTOR TO BE PER 250.122
9. USE CORRECT SIZED FUSES FOR CONDUCTOR
AMPACITY 310.16