Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03496
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/25/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
10/23/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOND BUSHING NEEDED AT CONCENTRICS - 250.97 2. BOND DISCONNECT ENCLOSURE - 250 3. USE LUGS LISTED FOR CONDUCTOR SIZED - 110.3 4. FINISH BATHROOM IS INSTA-HOT CORD & PLUG LISTED 5. EXIT/EM LIGHTING TO BE AS PER 700.12 6. MULTIPLE TERMINATIONS AT TRANSFORMER GROUNDED TERMINAL - 110.14 7. PLEASE PROVIDE LABLEING AS PER #12 OF SPECS OR REVISE SPECS 8. GROUND CONDUCTOR TO BE PER 250.122 9. USE CORRECT SIZED FUSES FOR CONDUCTOR AMPACITY 310.16 |