Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM03496
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/12/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
10/04/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUND ALL J-BOXES 2) CLOSE OFF ALL J-BOXES 3) MC TO BE STRAPPED WITHIN 12" OF TERMINATIONS 4) REMOVE COMPLETELY ALL ABANDONED WIRING AND EQUIPMENT 5) PROVIDE SUPPORT WIRES FOR ALL FIXTURES AND SECURE FIXTURES TO GRID 6) FINISH ALL WIRING-INCLUDING LOW VOLTAGE, FIRE, ETC. 7) MC NOT TO LAY ON GRID, SUPPORT WIRES FOR RACEWAYS TO BE SECURED AT BOTH END 8) ALL WIRING IN CEILING TO BE RAN IN A NEAT AND WORKMAN LIKE MANNER-CHECK BOX FILL, BOX MOUNTING, PROPER USE OF WIRE NUTS, ETC... 9) WIRING NOT PER PLAN 10) PROVIDE NAME AND PHONE NUMBER FOR THE LICENSED ELECTRICAL CONTRACTOR RESPONSIBLE FOR THIS WORK 11) PARTIAL INSPECTION-DO NOT COVER |