Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/07/2008 | FRAMING | Approved | ||
| 01/10/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO DWV TEST 2) NEED TO POUR CONCRETE BACK WHERE W/C WAS RELOCATED 3) NEED TO SUBMIT SIZING OF GAS LINES 4) GAS LINE CANNOT HAVE BLK PIE AND GALVANIZED MIXED 5) PEX WATER LINES NEED TO BE KEPT 12" AWAY FROM CAN LIGHTS 6) NEED TO INSULATE BEHIND SPA TUB 7) MECHANICAL DUCT AT TOILET STALL NEEDS TO BE FIXED AND STRAP ALL DUCTING |