Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/02/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 09/04/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE A TRAP ON CONDENSATE DRAIN LINE - PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN - INSULATE ALL SHEETMETAL DUCT IN FURNACE CLOSET WITH R4.2 INSULATION WITH VAPOR BARRIER - DO NOT CUT THE PLUG OFF OF THE CONDENSATE PUMP CORD. - PROVIDE A GROUNDED RECEPTACLE - INSTALL CONDENSATE DRAIN PIPE ON ROOF WITH A MIN. 1/8" PER FT. SLOPE & EXTEND DRAIN LINE TO WITHIN 6" OF THE GROUND. |