Permit: T07CM03489

Parcel: 126170140


Addresses:

4125 E PASEO DORADO

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/02/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
09/04/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PROVIDE A TRAP ON CONDENSATE DRAIN LINE
- PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN
- INSULATE ALL SHEETMETAL DUCT IN FURNACE CLOSET WITH R4.2 INSULATION WITH VAPOR BARRIER
- DO NOT CUT THE PLUG OFF OF THE CONDENSATE PUMP CORD.
- PROVIDE A GROUNDED RECEPTACLE
- INSTALL CONDENSATE DRAIN PIPE ON ROOF WITH A MIN. 1/8" PER FT. SLOPE & EXTEND DRAIN LINE TO WITHIN 6" OF THE GROUND.