Permit: T07CM03482

Parcel: 13506136A

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/18/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
02/13/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CONDENSATE DOES NOT HAVE ADEQUATE SLOPE
SUPPORT EVERY 4'
DO NOT BEND PIPE
USE FITTINGS TO CHANGE DIRECTION
NOT OK TO DRILL SCUPPERS AS PREVIOUSLY DISCUSSED, OK TO DRILL THROUGH PARAPET WALLS
02/11/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
PROVIDE MIN. 1/8" PER FT. SLOPE ON ALL CONDENSATE DRAINS
09/04/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PROVIDE CONDENSATE TO LANDSCAPE AREA AS PER PREVIOUS AGREEMENT