Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/02/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL |
|
| 10/01/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK INTERIOR OF UNITS RECALL FOR ROOFTOP INSPECTION |
|
| 09/16/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL KITCHEN COUNTER RECEPT. TO BE GFI PROTECTED ALL UNITS 2. MISSING RECEPT UNDER SINK - UNIT 120, 223 3. EXHAUST FANS LOCATED IN SHOWER SPACE TO BE GFI PROTECTED - CHECK ALL UNITS 4. MISSING OUTSIDE LIGHT- UNIT 121, 123 5. PANEL DIRECTORY - UNIT 122 6. COUNTER RECEPTACLE BEHIND RANGE UNIT 222 7. RECALL FOR ROOF INSPECTION 8. CAN ONLY INSPECT ONE BLDG. AT A TIME |
|
| 06/03/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) INSPECTION FOR RECONNECTION OF UNITS WITHOUT POWER 2) MARK UNIT NUMBERS ON SERVICES |