Permit: T07CM03469

Parcel: 11304115A


Addresses:

850 E GRAYBILL DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/17/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/10/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- NO COMPLIANCE WITH NOTES FROM PREVIOUS INSP.
- BE ADVISED THAT SMOKE DETECTORS ARE REQUIRED IN ALL BEDROOMS, MUST BE 3' AWAY MIN. FROM COOLER REGISTERS
18" FROM CORNERS FOR CEILING MTD
- PLEASE STRAP OTHER #4 GROUND TO WALL BELOW PANEL
09/04/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SERVICE PANEL DEAD FRONT COVER NOT PER MANUF.
ALSO, CIRCUIT BREAKER ARE MIXED BRANDS. MUST BE PER MANUF. OF PANEL
2. UF CABLE EXPOSED WHERE COMING INTO SHED
3. SUPPORT COOLER BOXES ON ROOF PROPERLY - USE A LISTED BRACE DESIGNED FOR THE PURPOSE
4. SMOKE DETECTORS MUST BE AT LEAST 3' AWAY FROM COOLER REGISTERS.