Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T07CM03465
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2009 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/09/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK FOR SHEETROCK UNITS 104, 105, 108, 109, 110, 111 2. PROVIDE BACKING AROUND CEILING BOXES PRIOR TO SHEETROCK |
|
| 04/01/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 03/30/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK FOR SHEETROCK UNITS 228-229 PROVIDE INSTALL INSTRUCTIONS FOR GREASE DUCT CLEANOUT DOOR. OK CEILING TILES. LEAVE OUT TO SEE ACCESS DOOR. |
|
| 03/19/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK FOR SHEETROCK UNITS 126-129 |
|
| 11/14/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CHECKED CONDENSATE DRAIN LINE OK TO INSULATE OK TO PROCEED WITH GREASE DUCT |
|
| 11/06/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CONDENSATE MUST STEP UP TO 1" AFTER THE 1ST TEE THEN UP TO 20 TONS ON 1; 40 TONS ON 1 1/4" |
|
| 11/04/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO SHEETROCK UNITS 214-217, 314-317 1ST LAYER OF FIRE WRAP OK OK FOR 2ND LAYER |
|
| 10/28/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK FOR SHEETROCK UNITS 113 A & B THRU 117 A & B |
|
| 10/06/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CONFIRMED METAL STUD WALL FOR TYPE 1 HOOD |
|
| 07/24/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK FOR SHEETROCK UNIT 124B |
|
| 07/01/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK SHEETROCK 220-223 HOWARD @ 602-826-3693 |
|
| 06/27/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 120A - OK 119B - OK 120B - OK 121B - OK 122B - OK 123B - OK |
|
| 06/26/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 119A - OK 120A - PROVIDE FIRE STOP BETWEEN FLOORS 121A - OK 122A - OK 123A - OK 124A - OK |
|
| 05/28/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* COMBUSTIBLE MATERIAL NOT ALLOWED IN A RETURN AIR PLENUM. REMOVE ALL WOOD & OTHER COMBUSTIBLES. PROVIDE SCREWS IN EXHAUST DUCT CONNECTIONS. INSTALL CONDENSATE DRAINS. |