Permit: T07CM03465

Parcel: 13324010C


Addresses:

250 N MAGUIRE AV


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T07CM03465

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/17/2009 PLUMBING - FINAL Approved
09/16/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
09/09/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PROVIDE BACK FLOW CORTS AND STERILIZATION PROCEDURE W/ BAC T REPORT.
COMPLETE WORK
09/04/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
08/31/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CLEANOUT IN ASPHALT IS NOT PER PLAN DETAIL
2) STERILIZATION OF ALL NEW WATER PIPING TO KIT AREA IS REQUIRED
3) ALL FS'S REQUIRE STRAINERS
4) ICE MAKER DRAIN NOT YET INSTALLED
5) BEVERAGE EQUIPMENT AND BACKFLOW PROTECTION NOT INSTALLED
6) PROVIDE A BACKFLOW LISTING OR INSTALL DEVICE AT STEAM OVEN
7) EXPOSE MISSING CLEANOUTS
8) INSTALL LISTED TAPPED PLUGS WITH APPROVED SCREW
9) SEAL ALL CLEANOUTS
10) TURN ON TRAP PRIMER VALVES
11) ONLY ONE SLIP NUT, NOT ALLOWED DOWNSTREAM OF TRAP
12) AT DW AVB REQUIRES 6" ABV FLOOD LEVEL FROM CRITICAL LEVEL
13) DW REQUIRES FULL SIZED 1/2" SUPPLY
08/28/2009 PLUMBING - FINAL Cancelled IVRS - RI canceled
08/27/2009 PLUMBING - FINAL Cancelled IVRS - RI canceled
06/24/2009 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
INSTALL TRAFFIC RATED C O COVER IN ASPHALTED AREA
RMS. 104-105 OK
06/04/2009 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
108-111 FINALS OK
414-417 FINALS OK
226-229 CORRECT CO PLUGS
06/03/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
05/13/2009 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
05/07/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. CAULKING
2. SLIP NUT ON TRAP ARM
05/04/2009 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
RMS. 314-317 OK
04/30/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
104 & 105 IN WALLS AND SHWR PANS OK
126-129 CLOSET FLANGES OK
03/09/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
02/18/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
317 & 316 SINKS NOT CAULKED
315 CHINA BOWL CAP
01/21/2009 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
214-217B OK
01/07/2009 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
UNITS 113-117B OK
CORRECTION IN UNIT 113A OK
12/24/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
113A-117A OK EXCEPT FOR SECOND SLIP NUT DOWNSTREAM OF P-TRAP AT KS IN RM 113A
12/23/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
10/30/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
UNITS #220, 221, 222, 223 OK
10/10/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
119-124 B FIXTURES OK
10/03/2008 PLUMBING - FINAL Partial Approval 119A-124A ROOMS OK
10/01/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
DELTA LAV. FAUCETS OK PER SUBMITTALS
ONLY ONE SLIP NOT ALLOWED DNSTRM OF P.TRAP
INSTALL ALL CLIPS ON SINKS
CAP OPEN VALVE
MAKE ALL CLEANOUTS ACCESSIBLE
PROVIDE CO PLUGS LISTED TO RECEIVE SCREW