Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T07CM03465
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/17/2009 | PLUMBING - FINAL | Approved | ||
| 09/16/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 09/09/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* PROVIDE BACK FLOW CORTS AND STERILIZATION PROCEDURE W/ BAC T REPORT. COMPLETE WORK |
|
| 09/04/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/31/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CLEANOUT IN ASPHALT IS NOT PER PLAN DETAIL 2) STERILIZATION OF ALL NEW WATER PIPING TO KIT AREA IS REQUIRED 3) ALL FS'S REQUIRE STRAINERS 4) ICE MAKER DRAIN NOT YET INSTALLED 5) BEVERAGE EQUIPMENT AND BACKFLOW PROTECTION NOT INSTALLED 6) PROVIDE A BACKFLOW LISTING OR INSTALL DEVICE AT STEAM OVEN 7) EXPOSE MISSING CLEANOUTS 8) INSTALL LISTED TAPPED PLUGS WITH APPROVED SCREW 9) SEAL ALL CLEANOUTS 10) TURN ON TRAP PRIMER VALVES 11) ONLY ONE SLIP NUT, NOT ALLOWED DOWNSTREAM OF TRAP 12) AT DW AVB REQUIRES 6" ABV FLOOD LEVEL FROM CRITICAL LEVEL 13) DW REQUIRES FULL SIZED 1/2" SUPPLY |
|
| 08/28/2009 | PLUMBING - FINAL | Cancelled | IVRS - RI canceled | |
| 08/27/2009 | PLUMBING - FINAL | Cancelled | IVRS - RI canceled | |
| 06/24/2009 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* INSTALL TRAFFIC RATED C O COVER IN ASPHALTED AREA RMS. 104-105 OK |
|
| 06/04/2009 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 108-111 FINALS OK 414-417 FINALS OK 226-229 CORRECT CO PLUGS |
|
| 06/03/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/13/2009 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* | |
| 05/07/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. CAULKING 2. SLIP NUT ON TRAP ARM |
|
| 05/04/2009 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* RMS. 314-317 OK |
|
| 04/30/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 104 & 105 IN WALLS AND SHWR PANS OK 126-129 CLOSET FLANGES OK |
|
| 03/09/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 02/18/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 317 & 316 SINKS NOT CAULKED 315 CHINA BOWL CAP |
|
| 01/21/2009 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 214-217B OK |
|
| 01/07/2009 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* UNITS 113-117B OK CORRECTION IN UNIT 113A OK |
|
| 12/24/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 113A-117A OK EXCEPT FOR SECOND SLIP NUT DOWNSTREAM OF P-TRAP AT KS IN RM 113A |
|
| 12/23/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 10/30/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* UNITS #220, 221, 222, 223 OK |
|
| 10/10/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 119-124 B FIXTURES OK |
|
| 10/03/2008 | PLUMBING - FINAL | Partial Approval | 119A-124A ROOMS OK | |
| 10/01/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* DELTA LAV. FAUCETS OK PER SUBMITTALS ONLY ONE SLIP NOT ALLOWED DNSTRM OF P.TRAP INSTALL ALL CLIPS ON SINKS CAP OPEN VALVE MAKE ALL CLEANOUTS ACCESSIBLE PROVIDE CO PLUGS LISTED TO RECEIVE SCREW |