Permit: T07CM03465

Parcel: 13324010C


Addresses:

250 N MAGUIRE AV


Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T07CM03465

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
08/12/2009 ELECTRIC - CABLE DROP Approved
09/05/2008 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
1. OK 2 - 4' PVC U.G FROM TEP XFMR TO SES
2. INSTALL WARNING RIBBON PER NEC 300.5
05/23/2008 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
1) OK CONSTRUCTION POWER FOR TRAILER
05/22/2008 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) HUB NOT CHANGED
2) ONLY ONE CONDUCTOR PER ACORN LUG
3) #8 NEEDS PHYSICAL PROTECTION
4) CANNOT TRIM CONDUCTORS
05/20/2008 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
05/15/2008 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SERVICE NOT TO BE MOUNTED ON TEMP TRAILER
2. GROUNDING ELECTRODE CONDUCTOR NOT PARALLEL
3. PROVIDE PHYSICAL PROTECTION FOR GEC & SE CABLE TO TRAILER PANEL
4. LABEL SERVICE WITH A PERMANENT METAL ADDRESS LABEL
5. LABEL ALL BREAKERS BOTH PANELS
6. SECURE GEC TO PANEL
7. MAIN BACK FED BREAKER TO USE MANUFACTURES HOLD DOWN
8. SEPARATE GROUNDS & NEUTRALS AT SUB-PANEL
9. FILL UNUSED OPENINGS BOTTOM OF SUB-PANEL