Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T07CM03465
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/12/2009 | ELECTRIC - CABLE DROP | Approved | ||
| 09/05/2008 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1. OK 2 - 4' PVC U.G FROM TEP XFMR TO SES 2. INSTALL WARNING RIBBON PER NEC 300.5 |
|
| 05/23/2008 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1) OK CONSTRUCTION POWER FOR TRAILER |
|
| 05/22/2008 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) HUB NOT CHANGED 2) ONLY ONE CONDUCTOR PER ACORN LUG 3) #8 NEEDS PHYSICAL PROTECTION 4) CANNOT TRIM CONDUCTORS |
|
| 05/20/2008 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 05/15/2008 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SERVICE NOT TO BE MOUNTED ON TEMP TRAILER 2. GROUNDING ELECTRODE CONDUCTOR NOT PARALLEL 3. PROVIDE PHYSICAL PROTECTION FOR GEC & SE CABLE TO TRAILER PANEL 4. LABEL SERVICE WITH A PERMANENT METAL ADDRESS LABEL 5. LABEL ALL BREAKERS BOTH PANELS 6. SECURE GEC TO PANEL 7. MAIN BACK FED BREAKER TO USE MANUFACTURES HOLD DOWN 8. SEPARATE GROUNDS & NEUTRALS AT SUB-PANEL 9. FILL UNUSED OPENINGS BOTTOM OF SUB-PANEL |